Grupo Industronic
UPS INDUSTRIAL
movil09
UPS Industriales con aplicaciones como transporte ferroviario, industria pesada, tren eléctrico urbano y plataformas marinas.
UPS INDUSTRIAL
1300Ind_slide
Industrial UPS with surge protection for use in railway industry, subway transport or naval platforms.

VIDEO

FEATURES

CARACT_UPS_1300_IND

FEATURES

  • Online double conversion
  • High reliability & performance DSP Control
  • Power factor correction
  • Cold start function (battery cold-start)
  • Battery power management
  • Smart ventilation
  • IGBT Inverter y input isolation transformer
  • Maintenance Bypass (included)
  • Automatic electronic Bypass
  • Automatic safety shut-off at input
  • SNMP network card included

TECHNICAL SPECIFICATIONS

  • Input Voltage Range
    120/208, 127/220, 220/380, 254/440, 277/480 VAC(± 20%).
  • Output Voltage Options
    120/208, 127/220, 220/380, 254/440, 277/480  VAC(± 1%).
  • Power Factor
    0.8 (optional 0.9).
  • Efficiency
    90%
  • Output Distortion
    Less than 3% THD (linear load).
  • Isolation Transformer
    Dry type
  • Overload Protection
    Input Thermal-magnetic breaker
  • Output Operating Frequency
    60 Hz ± 0.2% (optional 50 Hz ± 0.2%).
  • Transfer time
    0.0 ms (online).
  • Interface
    RS232 y RS485 Intelligent UPS (SNMP card/MODBUS optional).
  • Configuration
    Tower
  • Alarm Type
    Audible

SUPPLEMENTAL OPTIONS

  • Technology for parallel capacity or redundancy
  • Industronic Power Conditioner/Voltage Regulator to protect the UPS and extend battery life

SPECIFICATION TABLE

INPUT

MODEL UPS-IND 1330 UPS-IND 1346 UPS-IND 1350 UPS-IND 1353 UPS-IND 1358 UPS-IND 1362 UPS-IND 1366
Capacity (kW/kVA) 4/5 8/10 12/15 16/20 24/30 32/40 40/50
Overloading protection Input Thermal-magnetic breaker and bypass
Voltage (VAC) 120/208, 127/220, 220/380, 254/440, 277/480 ± 20%
Phases 3 phases LLLNT (4 wires + ground)
Frecuency (Hz) 60±10% (50±10% optional)
Power Factor 0.80 empty, > 0.95 full load
Overloading protection Output Thermal-magnetic breaker
Power Factor 0.8 (optional 0.9)

 

OUTPUT

MODEL UPS-IND 1330 UPS-IND 1346 UPS-IND 1350 UPS-IND 1353 UPS-IND 1358 UPS-IND 1362 UPS-IND 1366
Voltage (VAC) 120,127,220 1 Phase (LNT) or 120/208, 127/220, 220/380, 254/440, 277/480 3 Phases (LLLNT) ± 1%
Frecuency (Hz) 60 ± 0.2% (50 ± 0.2% optional)
Waveform Pure sine wave THD ≤ 3% (linear load)
Transfer Time (ms) 0.0 (online)
Rim factor 3
Connection type single-phase o triple-phase
Overload 125% for 10 min; 150% for 1 min

 

PHYSICAL AND MECHANICAL

MODEL UPS-IND 1330 UPS-IND 1346 UPS-IND 1350 UPS-IND 1353 UPS-IND 1358 UPS-IND 1362 UPS-IND 1366
Acoustical noise (dB) <65, to 3 feet
MTBF (hrs) 233000
Operating temperature (°C) 0 ~ 40
Relative humidity 0 ~ 95% without condensation
Maximum operating elevation (FASL) 2000 at 100% / 3000 at 96%
Cabinet Metallic, steel with electrostatic epoxy paint, for installation indoors, dead-front, self-supporting, IP21, black
Dimensions (width × depth × height in cm)** 80 x 80 x 180 100 x 80 x 180
UPS weight (kg)** 490 500 540 560 590 690 740

 

BATTERIES

MODEL UPS-IND 1330 UPS-IND 1346 UPS-IND 1350 UPS-IND 1353 UPS-IND 1358 UPS-IND 1362 UPS-IND 1366
Voltage (Vcd) 220
Battery type Nickel-cadmium internal gas recombination
Backup time at full load (min.) 5 (standard)
Maximum load current (A) 20 40 61 81 121 162 202
Battery bank Open, with tiered steel supports, welded, for installation indoors (vertical or horizontal layout)
Battery bank dimensions (cm)** According to specifications
Battery bank weight (kg)** According to specifications

 

TECNOLOGY

MODEL UPS-IND 1330 UPS-IND 1346 UPS-IND 1350 UPS-IND 1353 UPS-IND 1358 UPS-IND 1362 UPS-IND 1366
Conversion type Online double conversion, microprocessor-controlled
Rectifier T6- or 12-pulse SCR with phase control
Filters Contraharmonic mean (loop: 2 % RMS)
Isolation transformer Dry-type transformer included at input
Inverter switch components Static with PWM technology and IGBTs switched at 9000 Hzz
Battery status Information online or via real-time download with accuracy of ± 3 %
Heat dissipation (kBTU/h) 1.4 2.7 4.1 5.5 8.2 10.9 13.6
Static switch Static bypass with automatic transfer
Maintenance bypass Manual mechanical bypass
Paralleling in n + 1 up to 4 pieces of equipment
Certifications CE-IEC 62040-1. CE-IEC 62040-2, ISO 9001:2008
Communications interface RS-232, RS-485, dry-contact relay signal, SNMP/Modbus network card with one equipment port and two parallel ports
Screen (LCD touchscreen) Backlit: input and output voltage; load capacity; battery voltage; operating status; mimic panel
Dry contacts Inverter in operation; rectifier, inverter or static switch failure; normal operation; low battery; fan failure; rectifier power supply failure
Alarms Output overload; non-standard AC input; low battery; rectifier or charger failure; inverter failure; no power supply; battery in operation; ground failure; transfer to alternative line; overheating
Protection Thermal-magnetic circuit breakers at current input and for battery banks

**Approximate weight & dimensions without packaging.

Due to continuous improvements in our products, specifications are subject to change and change without notice.

DOWNLOADS

UPS-IND 1300 INDUSTRIAL

Model Data Sheet Manual
UPS-1300 (5-50KVA) Download
UPS1300 (60-120KVA) Download
UPS1300 (160-400KVA) Download

POWER CALCULATOR

Instantly calculate the capacity of the equipment that you require filling the following fields:

CURRENT:

PHASES:

KVAS:

Calculate

REQUEST PRICING

Name*:

E-mail*:

Phone*:

Company:

Country*:

Comments*:

Information about your inquiry:

*Required

logos
Top
INDUSTRONIC INDUSTRONIC
×