Grupo Industronic
UPS FOR RACK, UPS-IND 1122R
movil05
UPS FOR RACK, UPS-IND 1122R
Rack_slide

SETTINGS

CARACT_UPS_Rack

FEATURES

  • On-line doble conversión permite continuidad en la operación de la carga.
  • Amplio rango de tensión de entrada.
  • Bypass Electrónico / Automático; cero tiempo de transferencia
  • Cold-start capability, battery start-up
  • Software for the UPS-IND 1100 Rackmount monitoring system
  • SNMP network card included

TECHNICAL SPECIFICATIONS

Output

  • Capacity (VA/W): 3000/2100
  • Power factor: 0.80
  • Voltage (VAC): 120 ± 1 % (single-phase, 2 wires + ground)
  • Frequency (Hz): 50 or 60 ± 0.2 % (battery mode)
  • Waveform: Pure sine wave THD < 3 % (linear load)
  • Transfer time: 0 milliseconds (online)
  • Overload: 105–130 % for 60 seconds; 135–150 % for 30 seconds; over 150 % for 300 ms

Input

  • Voltage (VAC): 120 (+ 21 % – 33 %) / 80–145
  • Frequency (Hz): 60 ± 5 %
  • Power factor: 0.80 no-load, > 0.95 full load

Batteries

  • Voltage (VDC): 96
  • Battery type: Sealed, maintenance-free lead acid
  • Backup time: 7 minutes
  • Maximum load current (A): 0.5

Others

  • Communications interface: RS-232 (compatible with SNMP software and module)
  • Screen: LED indicators show the UPS operating status
  • Alarms: Low battery, abnormal power supply and UPS malfunction
  • Protection: Low battery, overload, short circuit and overheating
  • Noise: < 45 dB
  • Operating temperature: 0–40 °C (32–104 °F)
  • Relative Humidity: 0–95 %, without condensation
  • Monitoring software
  • Dimensions (height x width x depth in cm): 8.8 x 44 x 46
  • Weight (kg): 28

SPECIFICATION TABLES

INPUT

MODEL UPS-IND 1110 UPS-IND 1118 UPS-IND 1122 UPS-IND 1130 UPS-IND 1138 UPS-IND 1146
Capacity (W/VA) 800/1000 1600/2000 2400/3000 4000/5000 4800/6000 8000/10000
Overload protection Current limiter Thermal-magnetic breaker
Voltage (VAC) 120 or 220 (+21% -33%)
Phases Single-phase + neutral + ground
Frecuency (Hz) 60±10% (50±10% optional)
Input power factor 0.80 no-load > 0.95 full load
Overload protection Transfers the load to bypass

 

OUTPUT

MODELO UPS-IND 1110 UPS-IND 1118 UPS-IND 1122 UPS-IND 1130 UPS-IND 1138 UPS-IND 1146
Overload protection Transfers the load to bypass
Output power factor 0.8
Voltage (VAC) 120 or 220 ±1% 120±1% 220±1%
Frecuency (Hz) 60 ± 0.2% (50 ± 0.2% optional)
Waveform Pure sine wave THD < 3 % (linear load)
Transfer time (ms) 0.0 (online)
Overload 1105–130 % for 60 seconds; 135–150 % for 30 seconds; over 150 % for 300 ms

 

BATTERIES

MODEL UPS-IND 1110 UPS-IND 1118 UPS-IND 1122 UPS-IND 1130 UPS-IND 1138 UPS-IND 1146
Voltage (VDC) 36 72 96 192
Battery type Sealed maintenance-free lead acid
Backup time at full load (min.) 5 (for extended time consult the factory)
Maximum load current (A) 0.2 0.25 0.5 1.5
Battery bank Internal External
Battery bank dimensions (width x depth x height in cm) Internal 44 x 44 x 2U 44 x 44 x 3U 44 x 44 x 3U (x2)
Battery bank weight (kg) Internal 20 30 50 50 50(x2)

 

PHYSICAL AND MECHANICAL

MODEL UPS-IND 1110 UPS-IND 1118 UPS-IND 1122 UPS-IND 1130 UPS-IND 1138 UPS-IND 1146
Acoustical noise (dB) < 45 dB at 3 feet
MTBF(hrs) 50000
Operating temperature (°C) 0 ~ 40
Relative humidity 0 ~ 95% without condensation
Maximum operating elevation (FASL) 1000
Cabinet Steel with electrostatic epoxy paint
Dimensions (width × depth × height in cm) 44 x 44 x 2U 44 x 44 x 3U
UPS weight (kg) 10 11 18 20

 

TECNOLOGY

MODEL UPS-IND 1110 UPS-IND 1118 UPS-IND 1122 UPS-IND 1130 UPS-IND 1138 UPS-IND 1146
Conversion type Online double conversion
Inverter switch components PWM technology with IGBT switched at 19.2 kHz
Inverter configuration H-Bridge
Inverter type Pulse-width modulation (PWM)
Heat dissipation (kBTU/h) 0.3 0.6 0.9 1.5 1.8 3.0
Certifications CE-IEC 62040 – 1, ISO 9001:2008, NOM
Communications interface RS232 (compatible with optional SNMP/Modbus software and module)
Display LED (Monochromatic LCD)
Alarms For low battery for abnormal power supply for UPS malfunction
Protection Against low battery voltage, overload, short circuit and overheating

*Due to continuous improvements in our products, specifications are subject to change and change without notice.

DOWNLOADS

UPS-IND 1100 RACK

Model  Data Sheet Manual
UPS-IND 1100 RACK Download Download

POWER CALCULATOR

Instantly calculate the capacity of the equipment that you require filling the following fields:

CURRENT:

PHASES:

KVAS:

Calculate

REQUEST PRICING

Name*:

E-mail*:

Phone*:

Company:

Country*:

Comments*:

Information about your inquiry:

*Required

logos